Skip to content
Engineering Tools

Engineering Tools

Preliminary sizing tool

Advanced Baghouse Design Simulator

Preliminary sizing of actual gas flow, net/installed cloth area, bag count and can velocity; the final design needs dust data and engineering approval.

1. Gas Characteristics & Volume

Nm³/h

Wet volume (moisture included) at 0 °C and 101.325 kPa. If you enter a dry flow, give the moisture below. You can type 50,000 or 50.000.

Interpreted as: —

°C
m
°C

Acid or water dew point. May be left empty.

% H₂O

Only if you entered a dry normal flow: water vapour, % by volume. Empty = the flow is taken as wet.

Actual Gas Volume: — Am³/h

2. Filtration & Media Targets

m/min

—

mm

Interpreted as: —

With n ≥ 2, the remaining compartments carry the full flow while one is offline for cleaning or maintenance.

Preliminary Sizing Results

Net Cloth Area

— m²

—

Installed Cloth Area

— m²

—

Installed Bags

— pcs

— · —

A/C with all compartments online: — m/min

Critical Design Criteria

Can Velocity

— m/s

—

—

Recommended Media

—

—

Typical operating ΔP: 1.0–1.5 kPa (4–6 inH₂O)
Not calculated; K₁, K₂ are dust-specific (ISO 11057 / VDI 3926 test).
Pulse-jet cleaning: 2.8–8.3 bar · pulse 100–300 ms

Our experts should validate the system prior to setup.

Request Custom Quote

Why This Is Not a Basic Calculator

Tools that assume a constant airflow lead to wrongly sized filters. This tool converts the normal flow (Nm³/h) to the actual flow (Am³/h) at operating temperature and pressure with the ideal-gas correction (Boyle/Charles law). The cloth area is calculated with the actual flow.

What is can velocity? Even with enough cloth area, if the upward gas speed between the bags is too high, dust pulsed off the bags cannot fall into the hopper and is carried back onto neighbouring bags (re-entrainment). The tool flags values above 1.5 m/s as borderline and above 2.0 m/s as high risk. Fine or light dust may need less than 1.0 m/s.

Net and installed area: In a multi-compartment filter the remaining compartments carry the full flow while one is cleaned or serviced. The net A/C is the velocity in that state; the installed area is at least n/(n−1) times the net area and is calculated from the rounded-up bag count.

Calculation Method & Formulas

This tool performs preliminary pulse-jet baghouse sizing in five steps:

  1. Actual gas volume (ideal-gas correction): Qa = Qn × (T+273.15)/273.15 × (101.325/P) [m³/h]. P follows from the altitude with the standard-atmosphere formula. Qn is the wet (moisture-included) normal flow; for a dry normal flow the moisture factor 100/(100 − H₂O %) is applied. If the actual flow (Am³/h) is entered directly, this step is skipped.
  2. Net cloth area: Anet = Qa / (60 × vf) (Qa in m³/h, vf in m/min), where vf is the net air-to-cloth ratio (A/C). The default depends on the dust type: fine dust/fume 0.5–0.9; fly ash, fine cement, lime 0.6–0.9; general dust 0.8–1.1; coarse granular 0.9–1.2; flour, wood, paper 1.0–1.5 m/min (Cooper & Alley; EPA/452/B-02-001 Sec. 6).
  3. Installed area: with n ≥ 2 compartments the remaining compartments carry the full flow while one is offline: required installed area Anet × n/(n−1).
  4. Bag count: N = A / (π·D·L), rounded up; with several compartments the bags per compartment are rounded up too. The installed area shown is Ninst × π·D·L. Bag diameter 120–160 mm, length 2–8 m.
  5. Can velocity: vcan = (Qa/3600) / (housing cross-section − bag cross-sections) [m/s]. The housing cross-section is taken as bags × pitch² (pitch = D + 50 mm, i.e. 210 mm for Ø160; no wall clearance). This is an estimate. Typical band 0.5–2.0 m/s; above 1.5 m/s borderline, above 2.0 m/s re-entrainment risk. Fine or light dust may need less than 1.0 m/s.

Worked example: Qn = 50,000 Nm³/h at 120 °C, sea level → Qa ≈ 71,966 m³/h. For fly ash / fine cement vf = 0.75 m/min (45 m³/m²·h) → Anet ≈ 1,599 m²; with Ø160×3,000 mm bags (≈1.51 m² each) → 1,061 bags, can velocity ≈ 0.79 m/s. With 5 compartments the required installed area is ≈ 1,999 m²; with 5 × 266 = 1,330 bags the installed area is ≈ 2,006 m².

Typical operating pressure drop is 1.0–1.5 kPa; pulse-jet tank pressure 2.8–8.3 bar with 100–300 ms pulses. The tool does not calculate ΔP or compressed-air demand; K₁ and K₂ are dust-specific and found by testing (ISO 11057 / VDI 3926). The media suggestion follows continuous temperature limits: PE ~135 °C, PPS ~190 °C (acidic gas), aramid ~204 °C, P84 ~240 °C, PTFE ~250–260 °C, fibreglass ~260 °C. Results are for preliminary sizing; the final design must be validated with dust characterisation and process data.

Call Email